Conference paper
Faults in the Collection Grid of Offshore Wind Farms
This paper deals with transient conditions in the collection grid of offshore wind farms under different faults. A model of a standard wind farm was established in two versions, with a floating and a grounded collection grid respectively. Line to ground faults and three-phase to ground faults were applied at critical points at worst-case phase angle and the results compared.
The simulations show that it is better with a grounded collection grid, since lack of a ground reference will prevent the system from recovering after a line to ground fault.
Language: | English |
---|---|
Publisher: | IEEE Computer Society Press |
Year: | 2008 |
Pages: | 1-5 |
Proceedings: | 2008 Annual IEEE Student Paper Conference |
Journal subtitle: | Aispc08 |
ISBN: | 142442156X , 142442156x , 150908391X , 150908391x , 9781424421565 and 9781509083916 |
Types: | Conference paper |
DOI: | 10.1109/AISPC.2008.4460572 |
ORCIDs: | Holbøll, Joachim |
Cables Frequency response Grounding Joining processes Mathematical model Mesh generation Phase transformers Poles and towers SlimPowerSystems toolbox Wind farms Wind turbines floating collection grid grounded collection grid offshore wind farms power generation faults power grids power system analysis computing wind power plants