Conference paper

Faults in the Collection Grid of Offshore Wind Farms

In 2008 Annual Ieee Student Paper Conference — 2008, pp. 1-5
From

Electric Power Engineering, Department of Electrical Engineering, Technical University of Denmark1

Department of Electrical Engineering, Technical University of Denmark2

Centre for Electric Technology, Centers, Technical University of Denmark3

This paper deals with transient conditions in the collection grid of offshore wind farms under different faults. A model of a standard wind farm was established in two versions, with a floating and a grounded collection grid respectively. Line to ground faults and three-phase to ground faults were applied at critical points at worst-case phase angle and the results compared.

The simulations show that it is better with a grounded collection grid, since lack of a ground reference will prevent the system from recovering after a line to ground fault.