Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation
The present study investigated different combinations of floor/ceiling heating with mixing/displacement ventilation and their impacts on the indoor air distribution and ventilation effectiveness. Measurements were performed in a room during heating season in December. The results show that indoor vertical air temperature differences and air velocities for different hybrid systems are less than 3 C and 0.2 m/s when supply air temperature is 19 C, air change rate is 4.2 h-1, and heated surface temperature of floor/ceiling heating system is 25 C.
Ventilation effectiveness of mixing ventilation system combined with floor/ceiling heating systems is approximately equal to 1.0, and ventilation effectiveness of displacement ventilation system combined with floor/ceiling heating systems ranges from 1.0 to 1.2. The floor/ceiling heating systems combined with mixing ventilation system have more uniform indoor air distribution but smaller ventilation effectiveness compared with the floor/ceiling heating systems combined with displacement ventilation system.
With regard to the building heat loss increased by non-uniform indoor air distribution and small ventilation effectiveness, there should be an optimal combination of floor/ceiling heating with mixing/displacement ventilation to have the minimal building heat loss.The present study investigated different combinations of floor/ceiling heating with mixing/displacement ventilation and their impacts on the indoor air distribution and ventilation effectiveness.
Measurements were performed in a room during heating season in December. The results show that indoor vertical air temperature differences and air velocities for different hybrid systems are less than 3 C and 0.2 m/s when supply air temperature is 19 C, air change rate is 4.2 h-1, and heated surface temperature of floor/ceiling heating system is 25 C.
Ventilation effectiveness of mixing ventilation system combined with floor/ceiling heating systems is approximately equal to 1.0, and ventilation effectiveness of displacement ventilation system combined with floor/ceiling heating systems ranges from 1.0 to 1.2. The floor/ceiling heating systems combined with mixing ventilation system have more uniform indoor air distribution but smaller ventilation effectiveness compared with the floor/ceiling heating systems combined with displacement ventilation system.
With regard to the building heat loss increased by non-uniform indoor air distribution and small ventilation effectiveness, there should be an optimal combination of floor/ceiling heating with mixing/displacement ventilation to have the minimal building heat loss.
Language: | English |
---|---|
Publisher: | Springer |
Year: | 2014 |
Pages: | 59-67 |
Proceedings: | 8th International Symposium on Heating, Ventilation and Air ConditioningInternational Symposium on Heating, Ventilating and Air Conditioning |
Series: | Lecture Notes in Electrical Engineering |
Journal subtitle: | Volume 1: Indoor and Outdoor Environment |
ISBN: | 364239583X , 364239583x , 3642395848 , 9783642395833 and 9783642395840 |
ISSN: | 18761119 and 18761100 |
Types: | Conference paper and Book chapter |
DOI: | 10.1007/978-3-642-39584-0_7 |
ORCIDs: | Fang, Lei and Olesen, Bjarne W. |