Long term in situ measurements of hygrothermal conditions at critical points in four cases of internally insulated historic solid masonry walls

From

Department of Civil Engineering, Technical University of Denmark1

Section for Building Design, Department of Civil Engineering, Technical University of Denmark2

Aalborg University3

Ekolab4

In heritage buildings with solid masonry walls, where external insulation is not an option, insulating internally is an alternative way to improve indoor climate and reduce energy consumption and heat loss through external walls. This study presents results from hygrothermal measurements performed in four different buildings in Denmark where internal insulation has been installed.

The buildings are all heritage buildings from 1877–1932 and of solid masonry walls. The insulated façades differ in orientation, surface treatments, location, and insulation system. The insulation materials used are phenolic foam and polyurethane (PUR) foam, with calcium silicate channels in a grid of 40 × 40 mm.

Measurement results and hygrothermal assessments indicate that a vapour barrier does not contribute positively to the performance of the system and the more vapour open, the better performance on solid masonry. However, the performance is highly dependent on other parameters like insulation thickness and surface treatment, and above all: the external hygrothermal loads.

Therefore, before the application of internal insulation, every case should be carefully assessed in order to find the most suitable solution with regards to both thermal and hygrothermal performance.

Language: English
Year: 2018
Pages: 235-248
ISSN: 18726178 and 03787788
Types: Journal article
DOI: 10.1016/j.enbuild.2018.05.001