Sensory pollution from bag-type fiberglass ventilation filters: Conventional filter compared with filters containing various amounts of activated carbon

From

Section for Indoor Environment, Department of Civil Engineering, Technical University of Denmark1

Department of Civil Engineering, Technical University of Denmark2

As ventilation filters accumulate particles removed from the airstream, they become emitters of sensory pollutants that degrade indoor air quality. Previously we demonstrated that an F7 bag-type filter that incorporates activated carbon (a "combination filter") reduces this adverse effect compared to an equivalent filter without carbon.

The aim of the present study was to examine how the amount of activated carbon (AC) used in combination filters affects their ability to remove both sensory offending pollutants and ozone. A panel evaluated the air downstream of four different filters after each had continuously filtered outdoor suburban air over a period of 6 months.

Interim assessments (mid-term evaluation) were performed after 3 months. During both assessments, four unused filters, identical in type to the loaded filters, were also evaluated. The evaluated filters included a conventional F7 fiberglass filter and three modifications of a bag-type fiberglass combination filter: the "Heavy" corresponded to a commercially available filter containing 400 g of carbon per square meter of filter area, the "Medium" contained half as much carbon (200 g/m(2)), and the "Light" contained a quarter as much carbon (100 g/m(2)).

Each filter was weighed at the beginning of the soiling period and after 3 and 6 months of service. Additionally, up- and down-stream ozone concentrations and filter pressure drops were measured monthly. Following 6 months of service, the air downstream of each of the combination filters was judged to be significantly better than the air downstream of the 6-month-old F7 filter, and was comparable to that from an unused F7 filter.

Additionally, the combination filters removed more ozone from the air than the F7 filter, with their respective fractional removal efficiencies roughly scaling with their carbon content.

Language: English
Year: 2009
Pages: 2114-2120
ISSN: 1873684x and 03601323
Types: Journal article
DOI: 10.1016/j.buildenv.2009.03.002