Operative temperature drifts and occupant satisfaction with thermal environment in three office buildings using radiant heating/ cooling system

In Proceedings of Healthy Buildings Europe 2015 — 2015
From

Department of Civil Engineering, Technical University of Denmark1

Section for Building Energy, Department of Civil Engineering, Technical University of Denmark2

Section for Indoor Climate and Building Physics, Department of Civil Engineering, Technical University of Denmark3

The objective of this study was to analyse operative temperature drifts and occupant satisfaction with thermal environment in office buildings utilizing embedded radiant heating/cooling systems. Three office buildings were investigated: Town Hall in Viborg, Denmark (floor area 19400 m2), IDOM, Madrid, Spain (16000 m2), TiFS, Padua, Italy (2200 m2).

Continuous measurements of operative temperature were conducted at four workplaces in each building for one year. Occupants’ satisfaction was assessed by internet based questionnaire. Results showed that mostly exceeded limits were those for 4-hour drift (0.8 K/h), which were exceeded at least in 2% and up to 52% of occupied time in investigated buildings.

Limits for hourly and 2-hour drifts were exceeded in max. 2% of occupied time. Median values were in ranges of 0.12-0.29 K/h, 0.18-0.52 K/h and 0.27-0.84 K/h for 1, 2 and 4-hour drifts respectively. Occupants’ in all buildings were rather satisfied with temperature conditions. Median temperature satisfaction (0="Clearly satisfied" - 5="Clearly dissatisfied") was 2, 1 and 1 for Viborg, Madrid and Padua respectively.

Temperature satisfaction slightly decreased when rate of temperature change increased, thus higher temperature drifts seemed to lead to higher dissatisfaction, however the collected data did not allow for robust statistical analysis.

Language: English
Year: 2015
Proceedings: Healthy Buildings Europe 2015Healthy Buildings : The International Conference & Exhibition
Types: Conference paper
ORCIDs: Kolarik, Jakub , Toftum, Jørn and Olesen, Bjarne W.

DTU users get better search results including licensed content and discounts on order fees.

Log in as DTU user

Access

Analysis