Energy-Efficient Operation of a Direct Air-cooled Condenser Based on Divisional Regulation

From

North China Electric Power University1

Department of Chemical and Biochemical Engineering, Technical University of Denmark2

KT Consortium, Department of Chemical and Biochemical Engineering, Technical University of Denmark3

PROSYS - Process and Systems Engineering Centre, Department of Chemical and Biochemical Engineering, Technical University of Denmark4

The aerodynamic behavior of the fans array of the direct air-cooled condenser is different from that of a single fan because of the interaction effect between fans and the influence of wind. In this paper, a scale-down fan array experimental platform with measurement of the airflow and ambient wind speed is established to study the fan array partition schemes and cluster effect.

The divisional cluster factors are obtained by experiment and generalized by random forest regression. The dynamic models of the condenser backpressure are introduced by the moving-boundary method. To achieve transient performance, a divisional control strategy for the direct air-cooled condenser is realized by MPC-PID cascade control.

The simulation result shows that the fan power consumption is reduced by 14.7% compared to the existing control strategy. Furthermore, the wind speed disturbance is quickly suppressed cascade control.

Language: English
Year: 2021
Pages: 233-242
ISSN: 01407007 and 18792081
Types: Journal article
DOI: 10.1016/j.ijrefrig.2021.08.024
ORCIDs: Huusom, Jakob Kjøbsted

DTU users get better search results including licensed content and discounts on order fees.

Log in as DTU user

Access

Analysis