Impact of individually controlled facially applied air movement on perceived air quality at high humidity

From

Department of Civil Engineering, Technical University of Denmark1

Section for Indoor Environment, Department of Civil Engineering, Technical University of Denmark2

The effect of facially applied air movement on perceived air quality (PAQ) at high humidity was studied. Thirty subjects (21 males and 9 females) participated in three, 3-h experiments performed in a climate chamber. The experimental conditions covered three combinations of relative humidity and local air velocity under a constant air temperature of 26 degrees C, namely: 70% relative humidity without air movement, 30% relative humidity without air movement and 70% relative humidity with air movement under isothermal conditions.

Personalized ventilation was used to supply room air from the front toward the upper part of the body (upper chest, head). The subjects could control the flow rate (velocity) of the supplied air in the vicinity of their bodies. The results indicate an airflow with elevated velocity applied to the face significantly improves the acceptability of the air quality at the room air temperature of 26 degrees C and relative humidity of 70%.

Language: English
Year: 2010
Pages: 2170-2176
ISSN: 1873684x and 03601323
Types: Journal article
DOI: 10.1016/j.buildenv.2010.03.017