Journal article
Method for optimal design of pipes for low-energy district heating, with focus on heat losses
The synergy between highly energy-efficient buildings and low-energy district heating (DH) systems is a promising concept for the optimal integration of energy-saving policies and energy supply systems based on renewable energy (RE). Network transmission and distribution heat loss is one of the key factors in the optimal design of low-energy DH systems.
Various pipe configurations are considered in this paper: flexible pre-insulated twin pipes with symmetrical or asymmetrical insulation, double pipes, and triple pipes. These technologies represent potential energy-efficient and cost-effective solutions for DH networks in low-heat density areas. We start with a review of theories and methods for steady-state heat loss calculation.
Next, the article shows how detailed calculations with 2D-modeling of pipes can be carried out by means of computer software based on the finite-element method (FEM). The model was validated by comparison with experimental measurements, analytical formulas, and data from the literature. We took into account the influence of the temperature-dependent conductivity coefficient of polyurethane insulation foam, which enabled us to achieve a high degree of accuracy.
We also showed the influence of the soil temperature throughout the year. Finally, the article describes proposals for the optimal design of pipes for low-energy applications and presents methods for decreasing heat losses.
Language: | English |
---|---|
Year: | 2011 |
Pages: | 2407-2418 |
ISSN: | 18736785 and 03605442 |
Types: | Journal article |
DOI: | 10.1016/j.energy.2011.01.024 |
ORCIDs: | Svendsen, Svend |