Journal article
Passive Reactor Compensated Cascaded H-Bridge Multilevel LC-StatCom
University of New South Wales1
University of Newcastle2
Nanyang Technological University3
Department of Electrical Engineering, Technical University of Denmark4
Center for Electric Power and Energy, Centers, Technical University of Denmark5
Smart Electric Components, Center for Electric Power and Energy, Centers, Technical University of Denmark6
The cascaded H-bridge (CHB) low-capacitance StatCom (LC-StatCom) has a limited operating area in the inductive region compared to a conventional StatCom's V–I characteristic. This limitation for operation in the inductive region is considered to be the biggest disadvantage of CHB LC-StatCom. In this paper, the effect of adding parallel and series reactors on the LC-StatCom system's V–I characteristic is analyzed.
Then, a new configuration, which fully compensates for the lost operating area of the LC-StatCom, is introduced. A scaled down single-phase seven-level laboratory prototype is used to confirm practicability of the proposed system.
Language: | English |
---|---|
Publisher: | IEEE |
Year: | 2017 |
Pages: | 8338-8348 |
ISSN: | 19410107 and 08858993 |
Types: | Journal article |
DOI: | 10.1109/TPEL.2016.2641043 |
ORCIDs: | Agelidis, Vassilios |