Field study on thermal comfort and energy saving potential in 11 split air-conditioned office buildings in Changsha, China

In Energy 2019, Volume 182, pp. 471-482
From

Hunan University1

Department of Civil Engineering, Technical University of Denmark2

Indoor Environment, Department of Civil Engineering, Technical University of Denmark3

All existing thermal comfort standards are applicable to naturally ventilated buildings and air-conditioned buildings, except mixed-mode buildings. Split air-conditioned buildings, as a type of mixed-mode buildings, account for a large proportion of current buildings. It is urgent to explore the applicability of thermal comfort standards and determine the energy saving potential in split air-conditioned buildings.

In this research, the authors conducted a field study in Changsha, China. Eleven split air-conditioned office buildings were investigated from July to September 2016. 442 valid data sets were obtained. The results indicated that occupants preferred a “cooler” temperature of 26 °C, 0.6°Clower than neutral temperature of 26.7 °C.

Occupants have adapted to thermal environment and accepted higher temperature than that predicted by PPD. 95% of occupants were satisfied with the thermal environment. Compared to PMV model, the adaptive model was more applicable to split air-conditioned buildings. 8.6% of cooling energy could be conserved during summer in split air-conditioned buildings.

Language: English
Year: 2019
Pages: 471-482
ISSN: 18736785 and 03605442
Types: Journal article
DOI: 10.1016/j.energy.2019.05.204