AC Losses in Bi2Sr2Ca2Cu3O10+x Tapes and a 3.15-m-Long Single-Phase Cable

From

University of Copenhagen1

University of Southern Denmark2

Nano-Microstructures in Materials, Materials Research Division, Risø National Laboratory for Sustainable Energy, Technical University of Denmark3

Materials Research Division, Risø National Laboratory for Sustainable Energy, Technical University of Denmark4

Risø National Laboratory for Sustainable Energy, Technical University of Denmark5

NKT Photonics A/S6

Electric Components, Department of Electrical Engineering, Technical University of Denmark7

Department of Electrical Engineering, Technical University of Denmark8

The alternating-current losses in superconducting multifilament BiSCCO-2223 tapes and a 3.15-m single-phase test cable were measured at 77 K using an electrical transport method. The cable had an inner diameter of 42 mm; it was composed of a single layer of 31 multifilament tapes and had a critical current of $I_{c} = 4.1\ \hbox{kA}$.

The measured losses of the tapes were found to be in good agreement with the Norris ellipse (NE) model. The losses of the cable were, for high currents, found to be bounded by the monoblock and independent NE models.

Language: English
Publisher: IEEE
Year: 2011
Pages: 3599-3603
ISSN: 15582515 , 10518223 and 23787074