Conference paper
Early Prediction of Transient Voltage Sags caused by Rotor Swings
The paper investigates various methods to predict voltage sags at load buses caused by large generator rotor swings and following a transient disturbance. Three different prediction methods are proposed, which all use real-time measurements from PMUs. One of the methods uses a slightly extended version of the E-SIME method.
The other two methods use Measurements and process them by recursive least square estimation. It is shown that the prediction method employing E-SIME allows the earliest detection of a critical voltage sag with satisfactory accuracy.
Language: | English |
---|---|
Publisher: | IEEE |
Year: | 2014 |
Pages: | 1-5 |
Proceedings: | 2014 IEEE PES General Meeting |
ISBN: | 1479964158 , 1479964166 , 9781479964154 and 9781479964161 |
Types: | Conference paper |
DOI: | 10.1109/PESGM.2014.6939106 |
ORCIDs: | Weckesser, Johannes Tilman Gabriel and Jóhannsson, Hjörtur |
E-SIME method Generators PMU Rotors Transient analysis Voltage fluctuations Voltage measurement electric generators generator rotor swings least squares approximations load buses load forecasting power supply quality power system faults power system stability recursive least square estimation rotor swings rotors transient stability transient voltage sags transients voltage sag prediction